Electrochemical Modeling • • By Dr. Elena Vance

Understanding Peukert's Law: Why Battery Runtime Drops Under High Load

Discover how electrochemical resistance and ion diffusion kinetics cause battery capacity to drop at higher discharge rates, and how to compensate for it mathematically.

Understanding Peukert's Law: Why Battery Runtime Drops Under High Load

What is Peukert’s Law?

Peukert’s law, formulated by German scientist Wilhelm Peukert in 1897, captures the non-linear relationship between the discharge current of a battery and its actual delivered capacity.

In ideal calculations, runtime is often assumed to be strictly linear:

Runtime = Capacity (Ah) / Discharge Current (A)

However, as discharge current escalates, the effective capacity of the battery decreases.

The Mathematical Formula

Peukert’s equation is expressed as:

C_p = I^k * t

Where:

  • C_p is the Peukert capacity (at a 1-ampere discharge rate).
  • I is the actual discharge current.
  • k is the Peukert exponent (dimensionless, typically between 1.02 and 1.35).
  • t is the discharge time until cutoff voltage is reached.

Peukert Exponents Across Common Chemistries

Battery ChemistryTypical Peukert Exponent (k)Sensitivity to High Drain
Lithium Iron Phosphate (LiFePO4)1.02 – 1.05Extremely Low
Lithium-Ion (NMC / LCO)1.05 – 1.08Low
Lithium Polymer (LiPo)1.05 – 1.10Low to Moderate
Alkaline (AA / AAA)1.20 – 1.30Very High
Lead-Acid (Flooded / AGM)1.15 – 1.35Severe

Using BatteryPulse, you can dynamically adjust the Peukert exponent slider to project accurate operational lifespans under high continuous draws.